Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system

Hye Jin Cho, Jae Weon Jeong

Research output: Contribution to journalArticle

3 Citations (Scopus)

Abstract

The main purpose of this research is to evaluate the thermal-comfort environment in an office building served by a liquid-desiccant and indirect-and-direct evaporative-cooler-assisted 100% outdoor-air system (LD-IDECOAS). This research presents a method for evaluating the thermal environment via a series of energy simulations using the TRNSYS 17 program, integrated with an engineering equation-solver (EES) program. The supply air (SA) temperature is estimated according to the LD-IDECOAS seasonal operation modes proposed in previous research. The indoor-air conditions are estimated under the assumption that the relative humidity of room air was maintained at the set values by auxiliary humidification systems. Then, the predicted mean vote (PMV) values are estimated using the given indoor environment conditions. In this paper, the indoor-air conditions and PMV values for each LD-IDECOAS operation mode are represented. A detailed analysis of the impact of the indoor-air conditions on the PMV is provided in this paper. Furthermore, the simulation results for LD-IDECOAS were compared with those for a conventional variable-air-volume (VAV) system to evaluate the thermal environment in a building served by LD-IDECOAS. The PMV values with LD-IDECOAS showed that the thermal environment in a conditioned space is generally in compliance with ASHRAE Standard 55. Consequently, it is concluded that using LD-IDECOAS in an office building can produce energy savings with an acceptable level of thermal comfort.

Original languageEnglish
Pages (from-to)361-370
Number of pages10
JournalEnergy and Buildings
Volume172
DOIs
StatePublished - 2018 Aug 1

Fingerprint

Evaporative cooling systems
Thermal comfort
Office buildings
Liquids
Air

Keywords

  • Liquid desiccant and evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS)
  • Predicted mean vote (PMV)
  • Thermal comfort
  • Thermal environment simulation

Cite this

@article{ab5dce6c495e4e3ebbd52d5c5db7c3ba,
title = "Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system",
abstract = "The main purpose of this research is to evaluate the thermal-comfort environment in an office building served by a liquid-desiccant and indirect-and-direct evaporative-cooler-assisted 100{\%} outdoor-air system (LD-IDECOAS). This research presents a method for evaluating the thermal environment via a series of energy simulations using the TRNSYS 17 program, integrated with an engineering equation-solver (EES) program. The supply air (SA) temperature is estimated according to the LD-IDECOAS seasonal operation modes proposed in previous research. The indoor-air conditions are estimated under the assumption that the relative humidity of room air was maintained at the set values by auxiliary humidification systems. Then, the predicted mean vote (PMV) values are estimated using the given indoor environment conditions. In this paper, the indoor-air conditions and PMV values for each LD-IDECOAS operation mode are represented. A detailed analysis of the impact of the indoor-air conditions on the PMV is provided in this paper. Furthermore, the simulation results for LD-IDECOAS were compared with those for a conventional variable-air-volume (VAV) system to evaluate the thermal environment in a building served by LD-IDECOAS. The PMV values with LD-IDECOAS showed that the thermal environment in a conditioned space is generally in compliance with ASHRAE Standard 55. Consequently, it is concluded that using LD-IDECOAS in an office building can produce energy savings with an acceptable level of thermal comfort.",
keywords = "Liquid desiccant and evaporative cooling-assisted 100{\%} outdoor air system (LD-IDECOAS), Predicted mean vote (PMV), Thermal comfort, Thermal environment simulation",
author = "Cho, {Hye Jin} and Jeong, {Jae Weon}",
year = "2018",
month = "8",
day = "1",
doi = "10.1016/j.enbuild.2018.05.016",
language = "English",
volume = "172",
pages = "361--370",
journal = "Energy and Buildings",
issn = "0378-7788",

}

TY - JOUR

T1 - Evaluation of thermal comfort in an office building served by a liquid desiccant-assisted evaporative cooling air-conditioning system

AU - Cho, Hye Jin

AU - Jeong, Jae Weon

PY - 2018/8/1

Y1 - 2018/8/1

N2 - The main purpose of this research is to evaluate the thermal-comfort environment in an office building served by a liquid-desiccant and indirect-and-direct evaporative-cooler-assisted 100% outdoor-air system (LD-IDECOAS). This research presents a method for evaluating the thermal environment via a series of energy simulations using the TRNSYS 17 program, integrated with an engineering equation-solver (EES) program. The supply air (SA) temperature is estimated according to the LD-IDECOAS seasonal operation modes proposed in previous research. The indoor-air conditions are estimated under the assumption that the relative humidity of room air was maintained at the set values by auxiliary humidification systems. Then, the predicted mean vote (PMV) values are estimated using the given indoor environment conditions. In this paper, the indoor-air conditions and PMV values for each LD-IDECOAS operation mode are represented. A detailed analysis of the impact of the indoor-air conditions on the PMV is provided in this paper. Furthermore, the simulation results for LD-IDECOAS were compared with those for a conventional variable-air-volume (VAV) system to evaluate the thermal environment in a building served by LD-IDECOAS. The PMV values with LD-IDECOAS showed that the thermal environment in a conditioned space is generally in compliance with ASHRAE Standard 55. Consequently, it is concluded that using LD-IDECOAS in an office building can produce energy savings with an acceptable level of thermal comfort.

AB - The main purpose of this research is to evaluate the thermal-comfort environment in an office building served by a liquid-desiccant and indirect-and-direct evaporative-cooler-assisted 100% outdoor-air system (LD-IDECOAS). This research presents a method for evaluating the thermal environment via a series of energy simulations using the TRNSYS 17 program, integrated with an engineering equation-solver (EES) program. The supply air (SA) temperature is estimated according to the LD-IDECOAS seasonal operation modes proposed in previous research. The indoor-air conditions are estimated under the assumption that the relative humidity of room air was maintained at the set values by auxiliary humidification systems. Then, the predicted mean vote (PMV) values are estimated using the given indoor environment conditions. In this paper, the indoor-air conditions and PMV values for each LD-IDECOAS operation mode are represented. A detailed analysis of the impact of the indoor-air conditions on the PMV is provided in this paper. Furthermore, the simulation results for LD-IDECOAS were compared with those for a conventional variable-air-volume (VAV) system to evaluate the thermal environment in a building served by LD-IDECOAS. The PMV values with LD-IDECOAS showed that the thermal environment in a conditioned space is generally in compliance with ASHRAE Standard 55. Consequently, it is concluded that using LD-IDECOAS in an office building can produce energy savings with an acceptable level of thermal comfort.

KW - Liquid desiccant and evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS)

KW - Predicted mean vote (PMV)

KW - Thermal comfort

KW - Thermal environment simulation

UR - http://www.scopus.com/inward/record.url?scp=85047134108&partnerID=8YFLogxK

U2 - 10.1016/j.enbuild.2018.05.016

DO - 10.1016/j.enbuild.2018.05.016

M3 - Article

AN - SCOPUS:85047134108

VL - 172

SP - 361

EP - 370

JO - Energy and Buildings

JF - Energy and Buildings

SN - 0378-7788

ER -